ONLINE UPS 3 IN 1 OUT

LUCENT offers the largest selection of power management and protection solutions available in the industry. From the desktop to the data center, from AC-powered to DC-powered equipment, LUCENT is your one-stop partner for all your power needs.

The advance IGBT inverter, coupled with an isolation transformer, enhances the reliability and load adaptability. This unique construction for input and output isolation provides the advantages of noise rejection as well as clean and safe neutral line to the load.

Specifications

Features :

  • Fully Digital Signal Processing Using the Latest DSP Technology
  • IGBT Rectifier so High Input Power Factor
  • Dynamic Bypass With Eco Mode
  • Remote Management
  • Wide Input Voltage Range
  • Compatible With Engine Genertor
  • High Reliability For Maximum System Availability
  • Handles 3 : Crest Factor Loads
  • Intelligent Battery Management
  • Large LCD Display and Mimic Panel for Real-Time Information
  • Output Isolation Between UPS and Critical Load
  • Low Electro-Magnetic Interference
  • Complies With International Safety Standard
Capacity kVA 7.5 10 15 20 25 30
kW 6.75 9 13.5 18 22.5 27
TYPE Low Freq Uency Transfromer Based True On Line Double Conversion
Input Phase Three phase +N (Four Wire)
Input PF 0.9(Standard) / 1(Customized)
Input Voltage Range 415VAC +- 25%
Input Frequency 50Hz +- 10%
Input Ripple <5%
Soft Start 0~100%5 Second
Output Nominal Voltage 220V/230V/240V AC, 1P+N
Output Voltage Regulation +-1% For Linear & Non Linear Load
Output Frequency 50Hz +- 0.5%
Crest Factor >3:1
Output THD Pure Sine Wave
Dynamic Characteristics Instant Voltage < +-5% (From 0 to 100%), Recover Time < 10ms
Overload Capacity At 115% Load Normal Work, 125% Load 10 Minute 150% Load 1 Minute, 200% Load 1 second
Inverter Efficiency More Than 93% (Full Load)
Battery Nominal DC Voltage 360 360 360 360 360 360
Float Charging Voltage 406 406 406 406 406 406
Equalized Charging Voltage 426 426 426 426 426 426
charging Current -210 AMP Settable
Low Voltage Alarm 315 315 315 315 315 315
Low Voltage Trip 300 300 300 300 300 300
High Voltage Trip 435 435 435 435 435 435
Bypass Phase Single Phase (P+N)
Manual Maintenance Bypass Switch Provided
Static No Break
Protection Input Protection Input Voltage, Frequency Under / Over Limit Protection
Output Protection Over Current, Short, Short-Circuit, Over/Under Voltage
Battery Protection Over Charge, Over-Discharge Protection
Temperature Protection Inverter Over Temperature Protection
General parameters Working Environment Temp : 10-55′ C, Relative Humidity : 30%-90%
Communication Interface RS232/RS485, Optional Dry Contact , SNMP Card (For Remote)
Parellel Operation Hot Stand By
Protection Level IP21
Safety Performance V in -n , V out -n2 Vac, Creepage<1 mA, Insulting Resistance>2 MΩ (500V DC)
Noise (dB) 50-55 55-60 55-60
Dimension WxHxD (mm) 390x680x680 580x990x750
Weight (kg) 98 110 145 165 190 260