ONLINE UPS 3 IN 3 OUT

LUCENT offers the largest selection of power management and protection solutions available in the industry. From the desktop to the data center, from AC-powered to DCpowered equipment, LUCENT is your one-stop partner for all your power needs.

The advance IGBT inverter, coupled with an isolation transformer, enhances the reliability and load adaptability. This unique construction for input and output isolation provides the advantages of noise rejection as well as clean and safe neutral line to the load.

Specifications

Features :

  • Fully Digital Signal Processing Using the Latest DSP Technology
  • IGBT Rectifier so High Input Power Factor
  • Dynamic Bypass With Eco Mode
  • Remote Management
  • Wide Input Voltage Range
  • Compatible With Engine Genertor
  • High Reliability For Maximum System Availability
  • Handles 3 : Crest Factor Loads
  • Intelligent Battery Management
  • Large LCD Display and Mimic Panel for Real-Time Information
  • Output Isolation Between UPS and Critical Load
  • Low Electro-Magnetic Interference
  • Complies With International Safety Standard
Capacity kVA 10 15 20 30 40 50 60 80 100
kW 9 13.5 18 27 36 45 54 72 90
TYPE Low Freq Uency Transfromer Based True On Line Double Conversion
Input Phase Single Phase
Input PF 0.9(Standard) / 1(Customized)
Input Voltage Range 230VAC +- 25%
Input Frequency 50Hz +- 10%
Input Ripple <5%
Soft Start 0~100%5 Second
Output Nominal Voltage 380V / 400V / 415V AC (3P+N)
Output Voltage Regulation +-1% For Linear & Non Linear Load
Output Frequency 50Hz +- 0.5%
Crest Factor >3:1
Output THD Pure Sine Wave
Dynamic Characteristics Instant Voltage <+-5% (From 0 to 100%), Recover Time <10ms
Overload Capacity At 115% Load Normal Work, 125% Load 10 Minute
150% Load 1 Minute, 200% Load 1 second
Inverter Efficiency More Than 93% (Full Load)
Battery Nominal DC Voltage 360 360 360 360 360 360 360 360 360
Float Charging Volatage 406 406 406 406 406 406 406 406 406
Equalized Charging Voltage 426 426 426 426 426 426 426 426 426
Charging Current 2-10 Amp Settable
Low Voltage Alarm 315 315 315 315 315 315 315 315 315
Low Voltage Trip 300 300 300 300 300 300 300 300 300
High Voltage Trip 435 435 435 435 435 435 435 435 435
Bypass Phase Three Phase (P+N)
Manual Maintenance Bypass Switch Provided
Static No Break
Protection Input Protection Input Voltage,Frequency Under/Over Limit Protection
Output Protection Over Current, Shot-Circuit, Over/Under Voltage
Battery Protection Over Charge, Over-Discharge Protection
Temperature Protection Inverter Over Temperature Protection
General Parameters Working Environment Temp : 10-55’c, Relative Humidity : 30%-90%
Communication Interface RS232/RS485, Optional Dry Contact, SNMP Card (For Remote)
Parellel Operation Hot Stand By
Protection Level IP21
Safety Performance V in -n, V out -n 2000Vac, Creepage<10mA, Insulating Resistance > 2 MΩ (500V DC)
Noise (db) 50-55
Dimension WxHxD (mm) 580x990x750 875x975x800 1160x980x770 1400x1150x810
Weight (kg) 185 210 230 295 310 350 490 750 850